防火卷簾調(diào)試要注意哪些內(nèi)容?
防火卷簾控制器應(yīng)進(jìn)行通電功能備用電源火災(zāi)報(bào)警功能故障報(bào)警功能自動(dòng)控制功能手動(dòng)控制功能和自重下降功能調(diào)試,并應(yīng)符合下列要求:
The fire roller shutter controller should be debugged with power on function, backup power supply, fire alarm function, fault alarm function, automatic control function, manual control function, and self weight lowering function, and should meet the following requirements:
通電功能調(diào)試時(shí),應(yīng)將防火卷簾控制器分別與消防控制室的火災(zāi)報(bào)警控制器或消防聯(lián)動(dòng)控制設(shè)備相關(guān)的火災(zāi)探測器卷門機(jī)等連接并通電,防火卷簾控制器應(yīng)處于正常工作狀態(tài)。
When debugging the power on function, the fire shutter controller should be connected to the fire alarm controller in the fire control room or the fire detector door rolling machine related to the fire linkage control equipment, and powered on. The fire shutter controller should be in normal working state.
檢查數(shù)量:全數(shù)檢查。
Inspection quantity: All inspections.
檢查方法:直觀檢查。
Inspection method: Visual inspection.
備用電源調(diào)試時(shí),設(shè)有備用電源的防火卷簾,其控制器應(yīng)有主備電源轉(zhuǎn)換功能。主備電源的工作狀態(tài)應(yīng)有指示,主備電源的轉(zhuǎn)換不應(yīng)使防火卷簾控制器發(fā)生誤動(dòng)作。備用電源的電池容量應(yīng)保證防火卷簾控制器在備用電源供電條件下能正??煽抗ぷ?h,并應(yīng)提供控制器控制卷門機(jī)速放控制裝置完成卷簾自重垂降,控制卷簾降下限位所需的電源。
When debugging the backup power supply, the controller of the fireproof roller shutter equipped with the backup power supply should have the function of switching between the main and backup power supplies. The working status of the main and backup power supplies should be indicated, and the conversion of the main and backup power supplies should not cause the fire shutter controller to malfunction. The battery capacity of the backup power supply should ensure that the fire resistant roller shutter controller can operate normally and reliably for 1 hour under the backup power supply conditions, and the controller should be provided to control the speed release control device of the roller shutter machine to complete the weight drop of the roller shutter and control the power supply required to lower the roller shutter to the lower limit.
檢查數(shù)量:全數(shù)檢查。
Inspection quantity: All inspections.
檢查方法:切斷防火卷簾控制器的主電源,觀察電源工作指示燈變化情況和防火卷簾是否發(fā)生誤動(dòng)作。再切斷卷門機(jī)主電源,使用備用電源供電,使防火卷簾控制器工作1h,用備用電源啟動(dòng)速放控制裝置,觀察防火卷簾動(dòng)作運(yùn)行情況。
Inspection method: Cut off the main power supply of the fireproof roller shutter controller, observe the changes in the power indicator light and whether the fireproof roller shutter has malfunctioned. Cut off the main power supply of the rolling door machine again, use a backup power supply to power the fire shutter controller for 1 hour, start the quick release control device with the backup power supply, and observe the operation of the fire shutter.
火災(zāi)報(bào)警功能調(diào)試時(shí),防火卷簾控制器應(yīng)直接或間接地接收來自火災(zāi)探測器組發(fā)出的火災(zāi)報(bào)警信號,并應(yīng)發(fā)出聲光報(bào)警信號。
When debugging the fire alarm function, the fire shutter controller should directly or indirectly receive the fire alarm signal from the fire detector group and emit an audible and visual alarm signal.
檢查數(shù)量:全數(shù)檢查。
Inspection quantity: All inspections.
檢查方法:使火災(zāi)探測器組發(fā)出火災(zāi)報(bào)警信號,觀察防火卷簾控制器的聲光報(bào)警情況。
Inspection method: Make the fire detector group emit a fire alarm signal and observe the sound and light alarm of the fire shutter controller.
故障報(bào)警功能調(diào)試時(shí),防火卷簾控制器的電源缺相或相序有誤,以及防火卷簾控制器與火災(zāi)探測器之間的連接線斷線或發(fā)生故障,防火卷簾控制器均應(yīng)發(fā)出故障報(bào)警信號。
When debugging the fault alarm function, if the power supply of the fire shutter controller is out of phase or has incorrect phase sequence, as well as the connection line between the fire shutter controller and the fire detector is broken or malfunctioning, the fire shutter controller should send a fault alarm signal.
檢查數(shù)量:全數(shù)檢查。
Inspection quantity: All inspections.
檢查方法:任意斷開電源一相或?qū)φ{(diào)電源的任意兩相,手動(dòng)操作防火卷簾控制器按鈕,觀察防火卷簾動(dòng)作情況及防火卷簾控制器報(bào)警情況。斷開火災(zāi)探測器與防火卷簾控制器的連接線,觀察防火卷簾控制器報(bào)警情況。
Inspection method: Disconnect one phase of the power supply or switch between any two phases of the power supply, manually operate the button of the fire shutter controller, observe the action of the fire shutter and the alarm of the fire shutter controller. Disconnect the connection wire between the fire detector and the fire shutter controller, and observe the alarm status of the fire shutter controller.
自動(dòng)控制功能調(diào)試時(shí),當(dāng)防火卷簾控制器接收到火災(zāi)報(bào)警信號后,應(yīng)輸出控制防火卷簾完成相應(yīng)動(dòng)作的信號,并應(yīng)符合下列要求:
When debugging the automatic control function, when the fire shutter controller receives a fire alarm signal, it should output a signal to control the fire shutter to complete the corresponding action and meet the following requirements:
控制分隔防火分區(qū)的防火卷簾由上限位自動(dòng)關(guān)閉全閉。
The fire roller shutter that controls the partition of the fire compartment automatically closes from the upper limit to the fully closed position.
防火卷簾控制器接到感煙火災(zāi)探測器的報(bào)警信號后,控制防火卷簾自動(dòng)關(guān)閉中位(1.8m)處停止,接到感溫火災(zāi)探測器的報(bào)警信號后,繼續(xù)關(guān)閉全閉。
After receiving the alarm signal from the smoke fire detector, the fire shutter controller automatically closes to the middle position (1.8m) and stops. After receiving the alarm signal from the temperature fire detector, it continues to close until fully closed.
防火卷簾半降全降的動(dòng)作狀態(tài)信號應(yīng)反饋到消防控制室。
The action status signal of the fire roller shutter half down and full down should be fed back to the fire control room.
檢查數(shù)量:全數(shù)檢查。
Inspection quantity: All inspections.
檢查方法:分別使火災(zāi)探測器組發(fā)出半陣全降信號,觀察防火卷簾控制器聲光報(bào)警和防火卷簾動(dòng)作運(yùn)行情況以及消防控制室防火卷簾動(dòng)作狀態(tài)信號顯示情況。
Inspection method: Make the fire detector group emit a half array full down signal, observe the sound and light alarm of the fire shutter controller, the operation of the fire shutter action, and the display of the fire shutter action status signal in the fire control room.
手動(dòng)控制功能調(diào)試時(shí),手動(dòng)操作防火卷簾控制器上的按鈕和手動(dòng)按鈕盒上的按鈕,可控制防火卷簾的上升下降停止。
When debugging the manual control function, manually operating the buttons on the fire shutter controller and the buttons on the manual button box can control the rise and fall of the fire shutter to stop.
檢查數(shù)量:全數(shù)檢查。
Inspection quantity: All inspections.
檢查方法:手動(dòng)試驗(yàn)。
Inspection method: manual test.
自重下降功能調(diào)試時(shí),應(yīng)將卷門機(jī)電源設(shè)置于故障狀態(tài),防火卷簾應(yīng)在防火卷簾控制器的控制下,依靠自重下降全閉。
When debugging the self weight lowering function, the power supply of the rolling door machine should be set to a fault state, and the fire shutter should be controlled by the fire shutter controller to lower to fully closed by relying on its self weight.
檢查數(shù)量:全數(shù)檢查。
Inspection quantity: All inspections.
檢查方法:切斷卷門機(jī)電源,按下防火卷簾控制器下降按鈕,觀察防火卷簾動(dòng)作運(yùn)行情況。
Inspection method: Cut off the power supply of the rolling door machine, press the down button of the fire shutter controller, and observe the operation of the fire shutter.