防火卷簾的聯(lián)動(dòng)控制設(shè)計(jì)符合什么規(guī)定?
來(lái)源:http://luoboyy.com/ 發(fā)布時(shí)間:2022-12-31 11:11:54
防火卷簾門具有防火、隔煙、抑制火災(zāi)蔓延、保護(hù)人員疏散的特殊功能,廣泛應(yīng)用于高層建筑、大型等人員密集的場(chǎng)合。那么防火卷簾的聯(lián)動(dòng)控制設(shè)計(jì)符合什么規(guī)定?下面
濟(jì)南防火卷簾門安裝維修人員為你解答!
The fireproof rolling shutter door has the special functions of fire prevention, smoke separation, fire prevention and evacuation protection, and is widely used in high-rise buildings, shopping malls and other crowded places. What regulations does the linkage control design of the fire shutter meet? The following Jinan fire shutter door installation and maintenance personnel to answer for you!
用于疏散通道的防火卷簾控制器應(yīng)具有兩步關(guān)閉的功能,并應(yīng)向消防聯(lián)動(dòng)控制器發(fā)出反饋信號(hào)。防火卷簾控制器接收到火災(zāi)報(bào)警信號(hào)后,應(yīng)能控制防火卷簾自動(dòng)關(guān)閉到中位處停止;接收到二次報(bào)警信號(hào)后,應(yīng)能控制防火卷簾繼續(xù)關(guān)閉全閉狀態(tài)。
The fire shutter controller used for evacuation passage shall have the function of two-step closing, and shall send feedback signals to the fire linkage controller. After receiving the first fire alarm signal, the fire shutter controller shall be able to control the fire shutter to automatically close to the middle position and stop; After receiving the secondary alarm signal, it shall be able to control the fire shutter to continue to close to the fully closed state.
用于分隔防火分區(qū)的防火卷簾控制器在接收到防火分區(qū)內(nèi)任一火災(zāi)報(bào)警信號(hào)后,應(yīng)能控制防火卷簾到全關(guān)閉狀態(tài),并應(yīng)向消防聯(lián)動(dòng)控制器發(fā)出反饋信號(hào)。
After receiving any fire alarm signal in the fire compartment, the fire shutter controller used to separate the fire compartment shall be able to control the fire shutter to the fully closed state, and shall send a feedback signal to the fire linkage controller.
1.防火卷簾的升降應(yīng)由防火卷簾控制器控制。
1. The lifting of fire shutter shall be controlled by fire shutter controller.
2.疏散通道上設(shè)置的防火卷簾的聯(lián)動(dòng)控制設(shè)計(jì),應(yīng)符合下列規(guī)定:
2. The linkage control design of the fire shutter set on the evacuation exit shall meet the following requirements:
(1)、聯(lián)動(dòng)控制方式,防火分區(qū)內(nèi)任兩只獨(dú)立的感煙火災(zāi)探測(cè)器或任一只專門用于聯(lián)動(dòng)防火卷簾的感煙火災(zāi)探測(cè)器的報(bào)警信號(hào)應(yīng)聯(lián)動(dòng)控制防火卷簾下降距樓板面1.8m處;任一只專門用于聯(lián)動(dòng)防火卷簾的感溫火災(zāi)探測(cè)器的報(bào)警信號(hào)應(yīng)聯(lián)動(dòng)控制防火卷簾下降到樓板面;在卷簾的任一側(cè)距卷簾縱深0.5m~5m內(nèi)應(yīng)設(shè)置不少于2只專門用于聯(lián)動(dòng)防火卷簾的感溫火災(zāi)探測(cè)器。
(1) Linkage control mode: the alarm signal of any two independent smoke fire detectors or any smoke fire detector specially used for linkage fire shutter in the fire compartment shall be linked to control the fire shutter to descend to 1.8m from the floor; The alarm signal of any temperature fire detector specially used for linkage fire shutter shall be linked to control the fire shutter to descend to the floor; At least 2 heat fire detectors specially used for linkage fire shutter shall be set within 0.5m~5m from either side of the shutter to the depth of the shutter.
(2)、手動(dòng)控制方式,應(yīng)由防火卷簾兩側(cè)設(shè)置的手動(dòng)控制按鈕控制防火卷簾的升降。
(2) In manual control mode, the lifting and lowering of the fire shutter shall be controlled by the manual control buttons set on both sides of the fire shutter.
3.非疏散通道上設(shè)置的防火卷簾的聯(lián)動(dòng)控制設(shè)計(jì),應(yīng)符合下列規(guī)定:
3. The linkage control design of the fire shutter set on the non evacuation exit shall meet the following requirements:
(1)聯(lián)動(dòng)控制方式,應(yīng)由防火卷簾所在防火分區(qū)內(nèi)任兩只獨(dú)立的火災(zāi)探測(cè)器的報(bào)警信號(hào),作為防火卷簾下降的聯(lián)動(dòng)觸發(fā)信號(hào),并應(yīng)聯(lián)動(dòng)控制防火卷簾直接下降到樓板面。
(1) In linkage control mode, the alarm signal of any two independent fire detectors in the fire compartment where the fire shutter is located shall be used as the linkage trigger signal for the fire shutter to descend, and the fire shutter shall be controlled to descend directly to the floor.
(2)手動(dòng)控制方式,應(yīng)由防火卷簾兩側(cè)設(shè)置的手動(dòng)控制按鈕控制防火卷簾的升降,并應(yīng)能在消防控制室內(nèi)的消防聯(lián)動(dòng)控制器上手動(dòng)控制防火卷簾的降落。
(2) For manual control mode, the manual control buttons set at both sides of the fire shutter shall control the lifting and lowering of the fire shutter, and the fire linkage controller in the fire control room shall be able to manually control the lowering of the fire shutter.
4.防火卷簾下降距樓板面1.8m處、下降到樓板面的動(dòng)作信號(hào)和防火卷簾控制器直接連接的感煙、感溫火災(zāi)探測(cè)器的報(bào)警信號(hào),應(yīng)反饋消防聯(lián)動(dòng)控制器。