The installation of rolling shutter doors and fire resistant rolling shutter doors must be operated by professional rolling shutter door manufacturers. Normally, the installation and after-sales maintenance of rolling shutter doors will be included in the service items purchased by the manufacturer. Below, let's learn about the 7-step installation of the preferred fire resistant rolling shutter door guide rail with the Jinan fire resistant rolling shutter door installation and maintenance manufacturer.
1.防火卷簾簾板或簾面嵌入導軌的深度應符合表下表的規(guī)定。導軌間距大于下表的規(guī)定時,導軌間距每增加1000mm,每端嵌入深度應增加10mm,且卷簾安裝后不應變形。
1. The depth of the fireproof roller shutter panel or curtain surface embedded in the guide rail should comply with the regulations in the table below. When the distance between the guide rails is greater than the provisions in the table below, for every 1000mm increase in the distance between the guide rails, the embedding depth at each end should be increased by 10mm, and the roller shutter should not deform after installation.
2.導軌頂部應成圓弧形,其長度應保證卷簾正常運行。
2. The top of the guide rail should be in a circular arc shape, and its length should ensure the normal operation of the roller shutter.
3.導軌的滑動面應光滑、平直。簾片或簾面、滾輪在導軌內運行時應平穩(wěn)、順暢,不應有碰撞和沖擊現(xiàn)象。
3. The sliding surface of the guide rail should be smooth and straight. The curtain, curtain surface, and roller should run smoothly and smoothly within the guide rail, without any collision or impact.
4.單簾面卷簾的兩根導軌應互相平行,雙簾面卷簾不同簾面的導軌也應互相平行,其平行度誤差均不應大于5mm。
4. The two guide rails of a single curtain roller shutter should be parallel to each other, and the guide rails of different curtain surfaces of a double curtain roller shutter should also be parallel to each other, and their parallelism error should not exceed 5mm.
5.卷簾的導軌安裝后相對于基礎面的垂直度誤差不應大于1.5mm/m,全長不應大于20mm。
5. After installation, the verticality error of the guide rail of the roller shutter relative to the foundation surface should not exceed 1.5mm/m, and the total length should not exceed 20mm.
6.卷簾的防煙裝置與簾面應均勻緊密貼合,其貼合面長度不應小于導軌長度的80%。
6. The smoke prevention device of the roller shutter should be evenly and tightly fitted to the curtain surface, and the length of the fitting surface should not be less than 80% of the length of the guide rail.
7.防火卷簾的導軌應安裝在建筑結構上,并應采用預埋螺栓、焊接或膨脹螺栓連接。導軌安裝應牢固,固定點間距應為600-1000mm。
7. The guide rail of the fireproof roller shutter should be installed on the building structure and connected with embedded bolts, welding or expansion bolts. The installation of the guide rail should be firm, and the spacing between fixed points should be 600-1000mm.